How long do large hot water tanks last? Data from nearly 4,000 tanks in Canadian buildings

Hydrastone reviewed its service records for close to 4,000 large domestic hot water tanks in condos, apartment buildings, hospitals, hotels and commercial buildings across Canada. The records capture each tank's age, how worn its anode was and how much sediment had built up at the time of inspection.

Together they show how long large tanks last in real buildings, and what wears out along the way. The tank itself is long-lived. The anode and the sediment inside it are what need regular attention.

How old are the tanks Hydrastone services?

For tanks with a known year, Hydrastone's records show:

  • More than 4 in 10 are 30 or more years old.

  • Close to 6 in 10 are 20 or more years old.

  • About 1 in 7 are 50 or more years old.

  • Some are more than 70 years old and still in service.

The real share of older tanks is likely higher, closer to half. Tanks with no known year are more likely to be older, since older tanks are the ones most often missing a nameplate. The high-rise construction boom in Toronto and other Canadian cities over the last 20 years has also added a large number of newer tanks to the list, which pulls the average age down.

Most large tanks were set in place before the walls of the mechanical room went up, and the building was built around them. A tank that's still working at 30, 50 or 70 years isn't an exception. It's what a large tank can do when it's inspected, maintained and relined on schedule.

Most anodes were past the point where they should be replaced

The anode is a metal rod inside the tank that corrodes so the tank's steel doesn't. It's designed to be used up. As it wears away, there's less of it left to protect the steel. A common industry guideline is to replace an anode once it's more than 50% used up, rather than waiting until it's gone.

In Hydrastone's records, about 3 in 4 anodes were more than 50% used up when the technician checked them. About 1 in 10 were completely gone, which means nothing was protecting the steel.

That's why Hydrastone recommends an inspection every two years. Anodes wear out on a much shorter cycle than the tank itself, and an anode can't be seen from outside the tank.

About 3 in 10 tanks had moderate or excessive sediment

Sediment settles at the bottom of the tank. Some of it gets carried into the building's hot water, where it can:

  • clog pipes, faucet aerators and fixtures, and cause problems at individual taps

  • make the water look discoloured or cloudy, which is often the first thing residents complain about

Sediment also covers the bottom of the tank, where it gets in the way of inspecting the steel underneath. Hydrastone removes sediment as part of a regular maintenance visit.

What this means for condo boards and property managers

  • Inspect every two years. It's the only reliable way to catch a worn-out anode, sediment build-up or a failing lining while relining is still an option.

  • Plan to reline every 10 to 15 years. A Hydrastone reline typically costs under $10,000 CAD per tank, depending on the size and condition of the tank. That's a typical figure, not a quote or a guarantee. Replacing a large tank is often a six-figure job.

  • Think twice before replacing with a bank of small tanks. Small glass-lined tanks can't be relined. They often last up to about 10 years without maintenance and closer to 20 with it. A bank of them also adds piping, valves, fittings and insulation. When those aren't maintained, the result is heat loss and higher utility bills.

About the data

These figures come from the service records of Hydrastone, Canada's largest specialist in large domestic hot water tanks, as of November 2026. They include tanks on Hydrastone's active service list in multi-residential, commercial and institutional buildings across Canada. Not every record has every field, so each figure is based only on the records that have that field. Tank age is based on the year recorded for each tank. Anode wear is recorded by the technician at inspection, before the anode is replaced.

Related reading

Next
Next

What is cement relining, and how long does it last?